Lawrence Raybould January 6th 04 09:20 PM

Ariston Microgenus 23 combi boiler
 
Ariston Microgenus 23 combi boiler

My boiler recently developed a fault where I had central heating but
no domestic hot water (stone cold). I was advised to fit a new
diverter valve which I did.

The problem I have now is that I still have central heating but the
domestic hot water only runs hot for 2 to 3 minutes then runs luke
warm although the boiler is still fired up.

Does anyone have any suggestions what is causing this to happen?

BillR January 6th 04 09:35 PM

Ariston Microgenus 23 combi boiler
 
Lawrence Raybould wrote:
Ariston Microgenus 23 combi boiler

My boiler recently developed a fault where I had central heating but
no domestic hot water (stone cold). I was advised to fit a new
diverter valve which I did.

The problem I have now is that I still have central heating but the
domestic hot water only runs hot for 2 to 3 minutes then runs luke
warm although the boiler is still fired up.

Does anyone have any suggestions what is causing this to happen?


Flow switch?



Ed Sirett January 7th 04 12:17 AM

Ariston Microgenus 23 combi boiler
 
On Tue, 06 Jan 2004 12:20:57 +0000, Lawrence Raybould wrote:

Ariston Microgenus 23 combi boiler

My boiler recently developed a fault where I had central heating but
no domestic hot water (stone cold). I was advised to fit a new
diverter valve which I did.

The problem I have now is that I still have central heating but the
domestic hot water only runs hot for 2 to 3 minutes then runs luke
warm although the boiler is still fired up.

Does anyone have any suggestions what is causing this to happen?


1) Temperature sensor(s) out of spec?
2) Diverter valve letting primary water to CH during DHW mode.

I'm fairly sure this boiler does not have any sort of thermal store but
otherwise the behaviour is exactly as it would be if it had.

--
Ed Sirett - Property maintainer and registered gas fitter.
The FAQ for uk.diy is at www.diyfaq.org.uk
Gas fitting FAQ http://www.makewrite.demon.co.uk/GasFitting.html
Sealed CH FAQ http://www.makewrite.demon.co.uk/SealedCH.html



IMM January 7th 04 10:35 PM

Ariston Microgenus 23 combi boiler
 

"Ed Sirett" wrote in message
.co.uk...
On Tue, 06 Jan 2004 12:20:57 +0000, Lawrence Raybould wrote:

Ariston Microgenus 23 combi boiler

My boiler recently developed a fault where I had central heating but
no domestic hot water (stone cold). I was advised to fit a new
diverter valve which I did.

The problem I have now is that I still have central heating but the
domestic hot water only runs hot for 2 to 3 minutes then runs luke
warm although the boiler is still fired up.

Does anyone have any suggestions what is causing this to happen?


1) Temperature sensor(s) out of spec?
2) Diverter valve letting primary water to CH during DHW mode.

I'm fairly sure this boiler does not have any sort of thermal store but
otherwise the behaviour is exactly as it would be if it had.


It has an electric diverter valve. It has a flow switch which detects flow
and energises the diverter valve. Had the valve actually gone? The
actuator can be changed, rather than the whole valve inc water section.



---
--