i wish to install a pvc window in the gable end wall for my

loft question is do i need a lintel above the window ,

the window is 645mm X745mm.

including the cill and what are the regs on this

sort of thing thanks


  #2   Report Post  
Peter Taylor
 
Posts: n/a
Default lintel


"SCAREY-B.HERE-ON-THE.NET" wrote in message
...
i wish to install a pvc window in the gable end wall for my

loft question is do i need a lintel above the window ,

the window is 645mm X745mm.

including the cill and what are the regs on this

sort of thing thanks



What's the construction and thickness of the wall?

Yes, you'll need Building Regs approval for the structural opening and for the
window itself. You're not going to use the loft as a room are you? If so
you'll need to do a lot more work, like strengthening the floor and providing
Means of Escape in case of fire etc etc.

You should also talk to Planning, esp if you're in a conservation area or if the
window overlooks next door, and ask them if they need an application. Give them
a few more details than you've put on here though!

Peter

  #3   Report Post  
SCAREY-B.HERE-ON-THE.NET
 
Posts: n/a
Default lintel


"Peter Taylor" wrote in message
...

"SCAREY-B.HERE-ON-THE.NET" wrote in message
...
i wish to install a pvc window in the gable end wall for my

loft question is do i need a lintel above the window ,

the window is 645mm X745mm.

including the cill and what are the regs on this

sort of thing thanks



What's the construction and thickness of the wall?


outer layer standard brick with a 70mm cavity and iner layer standard brick

Yes, you'll need Building Regs approval for the structural opening and for

the
window itself. You're not going to use the loft as a room are you? yes

sort of computer room
If so
you'll need to do a lot more work, like strengthening the floor (already

had permission for the floor and it has been approved
and providing
Means of Escape in case of fire etc etc

..well would this not be the window

You should also talk to Planning, esp if you're in a conservation area or

if the
window overlooks next door, and ask them if they need an application.

Give them
a few more details than you've put on here though!

Peter



  #4   Report Post  
Peter Taylor
 
Posts: n/a
Default lintel

Peter Taylor wrote

You're not going to use the loft as a room are you? If so
you'll need to do a lot more work, like strengthening the floor and providing
Means of Escape in case of fire etc etc.


not to mention a new staircase
  #5   Report Post  
Peter Taylor
 
Posts: n/a
Default lintel

SCAREY-B.HERE-ON-THE.NET wrote

What's the construction and thickness of the wall?


outer layer standard brick with a 70mm cavity and iner layer standard brick


Certain it's 70mm? The internal brick tells me it's a fairly old house and
cavities were virtually always 50mm in those days, although there could have
been some build inaccuracy or some bulging of the outside skin. Anyway, either
way the easiest way to do this is with a Catnic CN7A lintel (for 50mm cavity) or
CN3A (for 70mm). If you can slide the lintel up inside the cavity you could use
a CG50/100 or CG70/100 which saves a bit of work.

A Catnic is the best for this job as it does not need a separate cavity DPC
above. It's 150mm deep and needs to be min 300mm longer than the width of the
opening to give 150mm bearing each end. They come in 300mm increments in
length.

You're going to need an access tower and hire 1 or 2 Jackall wall supports from
HSS to support the wall while you cut out the bricks to insert the lintel.
These will save having to support the brickwork all the way down to ground
level.

see www.catnic.com and look for Products Lintels Cavity Wall Combined Box
Lintels or Open Back Lintels

Peter



  #6   Report Post  
Owain
 
Posts: n/a
Default lintel

"SCAREY-B.HERE-ON-THE.NET" wrote
| Means of Escape in case of fire etc etc
| .well would this not be the window

Possibly not.

Escape Windows:

- An ‘Escape Window’ must be accessible via a ladder to assist rescue of the
occupants from the new room(s).
- Whether incorporated within a dormer or a roof light, it must have a clear
opening area of 0.33m2 with either the height or width being at least 450mm.
- The escape window should be within 1.7 metres of the eaves, measured along
the roof slope.
- The height of the sill of the vertical window should be between 800mm and
1100mm above the floor, and for a roof window between 600mm and 1100mm above
floor level.

http://www.stevenage.gov.uk/council/...g-control/bc-l
eaflet3.htm

See also

http://www.hullcc.gov.uk/buildingcontrol/leaflet_04.php

Owain



  #7   Report Post  
Owain
 
Posts: n/a
Default lintel

"Owain" wrote
| "SCAREY-B.HERE-ON-THE.NET" wrote
| | Means of Escape in case of fire etc etc
| | .well would this not be the window
| Possibly not.
|
http://www.stevenage.gov.uk/council/...g-control/bc-l
| eaflet3.htm
| See also
| http://www.hullcc.gov.uk/buildingcontrol/leaflet_04.php

And of course Hugo Nebula's Loft Conversion FAQ at
http://groups.google.com/groups?th=7a849f7121bbb36

Owain


  #9   Report Post  
Hugo Nebula
 
Posts: n/a
Default lintel

On Fri, 26 Dec 2003 11:24:37 -0000, a particular chimpanzee named
"Owain" randomly hit the keyboard and
produced:

And of course Hugo Nebula's Loft Conversion FAQ at
http://groups.google.com/groups?th=7a849f7121bbb36


Or even the new, improved version at
http://www.bathnes.gov.uk/buildingco...rsionguide.htm.
--
Hugo Nebula
"The fact that no-one on the internet wants a piece of this
shows you just how far you've strayed from the pack".
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
fireplace opening - lintel needed? Tim Hardisty UK diy 2 October 7th 03 11:28 PM
lintel help please Niel A. Farrow UK diy 3 September 6th 03 09:45 PM
more surprises - rotten joist and no lintel! Niel A. Farrow UK diy 3 August 15th 03 08:36 PM
Catnic Lintel, is this the right one? MikeT UK diy 2 August 4th 03 09:26 PM
Door lintel help please Icky UK diy 4 July 20th 03 03:48 PM


All times are GMT +1. The time now is 09:31 AM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"