  #1   Report Post  
Lee Blaver
 
Posts: n/a
Default Vaillant diverter valve

We have a (just out of warranty) Tubomax 828e combi (LCD display) and
the (electric) diverter valve is acting up. Sometimes it doesn't switch
between DHW and CH, even though the diagnostics say it has.
What seems to happen is that the boiler attempts to move the valve, but
doesn't move it far enough.
If it was seized or stiff I'd simply change it out, but if the boiler
is turned off, then back on, which exercises the valve, then the valve
works quite happily for the rest of the day.

Now, the valve is in stock, which suggests it is unreliable, but I also
notice that the board has been updated - anyone know what was changed?

I'm probably just going to swap the valve out, but I don't want to do
that and find out it was the board. Neither are cheap...

Lee




--
To reply use lee.blaver and ntlworld.com

  #2   Report Post  
Ed Sirett
 
Posts: n/a
Default Vaillant diverter valve

On Thu, 11 Dec 2003 20:09:50 +0000, Lee Blaver wrote:

We have a (just out of warranty) Tubomax 828e combi (LCD display) and
the (electric) diverter valve is acting up. Sometimes it doesn't switch
between DHW and CH, even though the diagnostics say it has.
What seems to happen is that the boiler attempts to move the valve, but
doesn't move it far enough.
If it was seized or stiff I'd simply change it out, but if the boiler
is turned off, then back on, which exercises the valve, then the valve
works quite happily for the rest of the day.

Now, the valve is in stock, which suggests it is unreliable, but I also
notice that the board has been updated - anyone know what was changed?

I'm probably just going to swap the valve out, but I don't want to do
that and find out it was the board. Neither are cheap...


It might also be worth checking that system is free of debris etc. whcih
might be jamming the valve.



--
Ed Sirett - Property maintainer and registered gas fitter.
The FAQ for uk.diy is at www.diyfaq.org.uk
Gas fitting FAQ http://www.makewrite.demon.co.uk/GasFitting.html
Sealed CH FAQ http://www.makewrite.demon.co.uk/SealedCH.html


  #3   Report Post  
Lee Blaver
 
Posts: n/a
Default Vaillant diverter valve

Ed Sirett wrote:
On Thu, 11 Dec 2003 20:09:50 +0000, Lee Blaver wrote:


We have a (just out of warranty) Tubomax 828e combi (LCD display) and
the (electric) diverter valve is acting up. Sometimes it doesn't switch
between DHW and CH, even though the diagnostics say it has.
What seems to happen is that the boiler attempts to move the valve, but
doesn't move it far enough.
If it was seized or stiff I'd simply change it out, but if the boiler
is turned off, then back on, which exercises the valve, then the valve
works quite happily for the rest of the day.

Now, the valve is in stock, which suggests it is unreliable, but I also
notice that the board has been updated - anyone know what was changed?

I'm probably just going to swap the valve out, but I don't want to do
that and find out it was the board. Neither are cheap...



It might also be worth checking that system is free of debris etc. whcih
might be jamming the valve.


Thanks for the reply, it was drained and refilled a few weeks ago to add
fresh inhibitor, might be connected I suppose. I'll take the valve off
later and check for anything obvious...

Lee
--
To reply use lee.blaver and ntlworld.com

  #4   Report Post  
ANt
 
Posts: n/a
Default Vaillant diverter valve

We had one of these fitted about 4 years ago I think. had the diverter
valve tweeked twice, replaced twice. It was definately a manufacturing
fault, I believe the valve gradually unwound itself or something.
Turning the boiler on and off seemed to fix it most of the time but
was obviously a real pain..specially as the thing tended not to work
for the morning rush.

The guy that fitted ours also fitted one at a similat time for my
father in-law. Exactly the same problem. Took a while for us to
convince vaillant it was a problem but then we had a guy come round
who admitted it was a known fault. The company that produced the valve
apparently changed the spec, and I believe this problem put them out
of business...but that could just be the boiler man talking the tail
up. Since our final replacement about 4 years ago, we haven't had a
problem.

I wouldn't have though you'd need a warranty given this was a fault
with the part. If you need any back up I could send you details of the
dates/times and possibly some job numbers from my service book.


Ant.


Lee Blaver wrote in message ...
We have a (just out of warranty) Tubomax 828e combi (LCD display) and
the (electric) diverter valve is acting up. Sometimes it doesn't switch
between DHW and CH, even though the diagnostics say it has.
What seems to happen is that the boiler attempts to move the valve, but
doesn't move it far enough.
If it was seized or stiff I'd simply change it out, but if the boiler
is turned off, then back on, which exercises the valve, then the valve
works quite happily for the rest of the day.

Now, the valve is in stock, which suggests it is unreliable, but I also
notice that the board has been updated - anyone know what was changed?

I'm probably just going to swap the valve out, but I don't want to do
that and find out it was the board. Neither are cheap...

Lee

  #5   Report Post  
Lee Blaver
 
Posts: n/a
Default Vaillant diverter valve

ANt wrote:

We had one of these fitted about 4 years ago I think. had the diverter
valve tweeked twice, replaced twice. It was definately a manufacturing
fault, I believe the valve gradually unwound itself or something.
Turning the boiler on and off seemed to fix it most of the time but
was obviously a real pain..specially as the thing tended not to work
for the morning rush.

The guy that fitted ours also fitted one at a similat time for my
father in-law. Exactly the same problem. Took a while for us to
convince vaillant it was a problem but then we had a guy come round
who admitted it was a known fault.


Snip

Thanks, a phone call to Vaillant is in order on monday then.


Lee
--
To reply use lee.blaver and ntlworld.com

Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
CH System - what is this gate valve for? Colin M UK diy 7 November 25th 03 10:04 AM
Boiler diverter valve Ian Nutt UK diy 8 November 13th 03 01:18 PM
3 way diverter question Wdyw UK diy 7 October 14th 03 10:06 AM
NO HW NO CH, Honeywell diverter valve Clive Long,UK UK diy 6 October 7th 03 04:03 PM
Leaving a Honeywell CH valve energised, wiring choices Toby UK diy 1 July 14th 03 06:20 PM


All times are GMT +1. The time now is 02:45 AM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"