Connections for main earth bonding to gas/water?



 
 
LinkBack Thread Tools Display Modes
  #1  
Old February 5th 07, 10:52 AM posted to uk.d-i-y
external usenet poster
 
Posts: 4,273
Default Connections for main earth bonding to gas/water?

I need to connect up earth bonding conductors to my incoming gas and
water supplies, and have just checked Whitfield's "Electrician's Guide"
to double-check which side of the respective stop cocks to attach the
bonding.

For an all-copper system like mine, Whitfield shows the water pipe
earthed on the *street* side of the stopcock, whereas the gas pipe it is
on the *house* side of the stopcock (Fig 5.13). I'm assuming that's
correct but can't understand the logic behind it - before I unpack my
earth clamps please can someone explain?!

Thanks
David
Ads
  #2  
Old February 5th 07, 12:11 PM posted to uk.d-i-y
external usenet poster
 
Posts: 2,490
Default Connections for main earth bonding to gas/water?

In an earlier contribution to this discussion,
Lobster wrote:

I need to connect up earth bonding conductors to my incoming gas and
water supplies, and have just checked Whitfield's "Electrician's
Guide" to double-check which side of the respective stop cocks to
attach the bonding.

For an all-copper system like mine, Whitfield shows the water pipe
earthed on the *street* side of the stopcock, whereas the gas pipe it
is on the *house* side of the stopcock (Fig 5.13). I'm assuming that's
correct but can't understand the logic behind it - before I unpack my
earth clamps please can someone explain?!

Thanks
David


Assuming that the stopcocks and the pipes either side are all made of
conducting material, does it really matter?
--
Cheers,
Roger
______
Email address maintained for newsgroup use only, and not regularly
monitored.. Messages sent to it may not be read for several weeks.
PLEASE REPLY TO NEWSGROUP!


  #3  
Old February 5th 07, 12:27 PM posted to uk.d-i-y
external usenet poster
 
Posts: 3,348
Default Connections for main earth bonding to gas/water?

On Mon, 5 Feb 2007 09:52:34 UTC, Lobster
wrote:

I need to connect up earth bonding conductors to my incoming gas and
water supplies, and have just checked Whitfield's "Electrician's Guide"
to double-check which side of the respective stop cocks to attach the
bonding.

For an all-copper system like mine, Whitfield shows the water pipe
earthed on the *street* side of the stopcock, whereas the gas pipe it is
on the *house* side of the stopcock (Fig 5.13). I'm assuming that's
correct but can't understand the logic behind it - before I unpack my
earth clamps please can someone explain?!


The OSG clearly states that "the connection to the gas, water, oil etc.
service should be within 600mm of the service meter, or at the point of
entry to the building if the service meter is external, and must be on
the consumer's side before any branch pipework...". Refers to 547-02-02
in the regs. The regs also say that if there is an insulating section at
that point, or a meter, the connection should be made to the consumer's
hard metal pipework. So, if there isn't a meter, have it as near to the
point of entry as possible, so that will determine which side of the
stopcock you choose. Perhaps that's what Whitfield is getting at.

(I have the blue versions of OSG and regs).
--
The information contained in this post is copyright the
poster, and specifically may not be published in, or used by
http://www.diybanter.com
  #4  
Old February 5th 07, 02:35 PM posted to uk.d-i-y
external usenet poster
 
Posts: 19,928
Default Connections for main earth bonding to gas/water?

In article ,
Lobster wrote:
For an all-copper system like mine, Whitfield shows the water pipe
earthed on the *street* side of the stopcock, whereas the gas pipe it is
on the *house* side of the stopcock (Fig 5.13). I'm assuming that's
correct but can't understand the logic behind it - before I unpack my
earth clamps please can someone explain?!



I must be Irish - to be sure to be sure - but always bond both sides of
the stopcock and gas meter/cutoff valve. Clamps ain't expensive.

--
*Upon the advice of my attorney, my shirt bears no message at this time

Dave Plowman London SW
To e-mail, change noise into sound.
  #5  
Old February 5th 07, 05:35 PM posted to uk.d-i-y
external usenet poster
 
Posts: 7,702
Default Connections for main earth bonding to gas/water?


"Dave Plowman (News)" wrote in message
...
In article ,
Lobster wrote:
For an all-copper system like mine, Whitfield shows the water pipe
earthed on the *street* side of the stopcock, whereas the gas pipe it is
on the *house* side of the stopcock (Fig 5.13). I'm assuming that's
correct but can't understand the logic behind it - before I unpack my
earth clamps please can someone explain?!



I must be Irish - to be sure to be sure - but always bond both sides of
the stopcock and gas meter/cutoff valve. Clamps ain't expensive.

--
*Upon the advice of my attorney, my shirt bears no message at this time

Dave Plowman London SW
To e-mail, change noise into sound.


I believe that the gas companies now put electrical insulators in their
meters and do not want you to bond at their side of the supply to stop
currents in their pipework.

Adam

  #6  
Old February 5th 07, 07:22 PM posted to uk.d-i-y
external usenet poster
 
Posts: 1,219
Default Connections for main earth bonding to gas/water?

ARWadsworth wrote:

I believe that the gas companies now put electrical insulators in their
meters and do not want you to bond at their side of the supply to stop
currents in their pipework.


Correct, and has been the case for quite some time. Where fitted it's
an insulating insert on the input side of the meter (AIUI).

--
Andy
  #7  
Old February 5th 07, 08:11 PM posted to uk.d-i-y
external usenet poster
 
Posts: 189
Default Connections for main earth bonding to gas/water?


Assuming that the stopcocks and the pipes either side are all made of
conducting material, does it really matter?


It does if its Gas, see Andys reply.

Dave
 




Thread Tools
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

vB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On

Similar Threads
Thread Thread Starter Forum Replies Last Post
running main bonding cable along same route as water ironer UK diy 4 November 14th 06 03:17 AM
Cross-bonding/earth bonding gas meter Jim UK diy 1 July 28th 06 10:19 PM
Earth provision after replacing water main with MDPE Zikki Malambo UK diy 0 January 13th 05 09:20 AM
Earth provision after replacing water main with MDPE Kevin Brady UK diy 12 January 12th 05 10:24 PM
Earth Bonding Water Heater Doctor D. UK diy 7 March 20th 04 10:19 PM


All times are GMT +1. The time now is 09:14 PM.


Powered by vBulletin® Version 3.6.4
Copyright ©2000 - 2014, Jelsoft Enterprises Ltd.SEO by vBSEO ©2010, Crawlability, Inc.
Copyright 2004-2014 DIYbanter.
The comments are property of their posters.