  #1   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 1
Default combi boiler keeps on turning on

Hi - not sure if there is anything wrong with my boiler or not. i have
a vailant combi boiler and no matter what heat setting it is at it
comes on for a while with the burners going, seems to turn off and then
starts straight back up again - continuously. I thought that it would
keep on till it had reached the temp and then just keep blasting as and
when needed - not keep going on and off the whole time? Any help would
be appreciated. Thanks Debbie

  #2   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 145
Default combi boiler keeps on turning on


"debbieg" wrote in message
ups.com...
Hi - not sure if there is anything wrong with my boiler or not. i have
a vailant combi boiler and no matter what heat setting it is at it
comes on for a while with the burners going, seems to turn off and then
starts straight back up again - continuously. I thought that it would
keep on till it had reached the temp and then just keep blasting as and
when needed - not keep going on and off the whole time? Any help would
be appreciated. Thanks Debbie


What model and how often does it come on and off? I mean, they are meant to
turn off when the CH is up to temperature, then they come back on when the
temperature drops, so it would help if we knew exactly what its doing.

Andy.


  #3   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 3,356
Default combi boiler keeps on turning on

On 17 Dec 2006 04:59:23 -0800 someone who may be "debbieg"
wrote this:-

i have
a vailant combi boiler and no matter what heat setting it is at it
comes on for a while with the burners going, seems to turn off


How does it "seem to turn off"?

Do you mean that the burners turn off? When they turn off the pump
will probably still be running.

and then starts straight back up again


After how long?

- continuously.


For how long?

Depending on the times this could be caused by a variety of things.
For example some combination boilers have a hot water reservoir that
they keep warm by intermittent firing. We will have more chance of
guessing what it is with more information.



--
David Hansen, Edinburgh
I will *always* explain revoked encryption keys, unless RIP prevents me
http://www.opsi.gov.uk/acts/acts2000/00023--e.htm#54
  #4   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 2,231
Default combi boiler keeps on turning on

On Sun, 17 Dec 2006 04:59:23 -0800, debbieg wrote:

Hi - not sure if there is anything wrong with my boiler or not. i have
a vailant combi boiler and no matter what heat setting it is at it
comes on for a while with the burners going, seems to turn off and then
starts straight back up again - continuously. I thought that it would
keep on till it had reached the temp and then just keep blasting as and
when needed - not keep going on and off the whole time? Any help would
be appreciated. Thanks Debbie


What model?
A stock fault on the VCW 242s is that the main PCB (the hardest to change)
goes down with a fault that causes the CH to run continously.


--
Ed Sirett - Property maintainer and registered gas fitter.
The FAQ for uk.diy is at http://www.diyfaq.org.uk
Gas fitting FAQ http://www.makewrite.demon.co.uk/GasFitting.html
Sealed CH FAQ http://www.makewrite.demon.co.uk/SealedCH.html
Choosing a Boiler FAQ http://www.makewrite.demon.co.uk/BoilerChoice.html
Gas Fitting Standards Docs he http://www.makewrite.demon.co.uk/GasFittingStandards
  #5   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 2,112
Default combi boiler keeps on turning on

Hah, I had a Vaillant which I replaced with a Halstead. This is almost
exactly the opposite of the fault I have at the moment (random tripping and
locking out). When I find out what is wrong I will post the answer; good
luck!




  #6   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 24
Default combi boiler keeps on turning on


"debbieg" wrote in message
ups.com...
Hi - not sure if there is anything wrong with my boiler or not. i have
a vailant combi boiler and no matter what heat setting it is at it
comes on for a while with the burners going, seems to turn off and then
starts straight back up again - continuously. I thought that it would
keep on till it had reached the temp and then just keep blasting as and
when needed - not keep going on and off the whole time? Any help would
be appreciated. Thanks Debbie


If you have a wireless programmer/thermostat, check the batteries in it. We
have an Alpha boiler with wireless programmer/thermostat and if we happen to
miss the low battery indicator on it (which is easy to do) the boiler goes
into a sort of a hard-coded "failsafe" (I know that's not the phrase I need
but can't think of anything better at the moment) 2 minutes on, 9 minutes
off, cycle - and continues like that until the batteries are replaced.

JellyBelly


  #7   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 310
Default combi boiler keeps on turning on

JellyBelly wrote:
"debbieg" wrote in message
ups.com...
Hi - not sure if there is anything wrong with my boiler or not. i have
a vailant combi boiler and no matter what heat setting it is at it
comes on for a while with the burners going, seems to turn off and then
starts straight back up again - continuously. I thought that it would
keep on till it had reached the temp and then just keep blasting as and
when needed - not keep going on and off the whole time? Any help would
be appreciated. Thanks Debbie


If you have a wireless programmer/thermostat, check the batteries in it. We
have an Alpha boiler with wireless programmer/thermostat and if we happen to
miss the low battery indicator on it (which is easy to do) the boiler goes
into a sort of a hard-coded "failsafe" (I know that's not the phrase I need
but can't think of anything better at the moment) 2 minutes on, 9 minutes
off, cycle - and continues like that until the batteries are replaced.

JellyBelly


I have a Vailant combi boiler, it does this at odd times through the
day, even when CH is switched off and no hot water is being drawn. when
it was installed the installer told me this would happen as it keeps a
small reservoir of hot water. Not sure of the model, if it is important
I can root through my boxes and find out.
  #8   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 2,231
Default combi boiler keeps on turning on

On Mon, 18 Dec 2006 17:25:01 +0000, Broadback wrote:

JellyBelly wrote:
"debbieg" wrote in message
ups.com...
Hi - not sure if there is anything wrong with my boiler or not. i have
a vailant combi boiler and no matter what heat setting it is at it
comes on for a while with the burners going, seems to turn off and then
starts straight back up again - continuously. I thought that it would
keep on till it had reached the temp and then just keep blasting as and
when needed - not keep going on and off the whole time? Any help would
be appreciated. Thanks Debbie


If you have a wireless programmer/thermostat, check the batteries in it. We
have an Alpha boiler with wireless programmer/thermostat and if we happen to
miss the low battery indicator on it (which is easy to do) the boiler goes
into a sort of a hard-coded "failsafe" (I know that's not the phrase I need
but can't think of anything better at the moment) 2 minutes on, 9 minutes
off, cycle - and continues like that until the batteries are replaced.

JellyBelly


I have a Vailant combi boiler, it does this at odd times through the
day, even when CH is switched off and no hot water is being drawn. when
it was installed the installer told me this would happen as it keeps a
small reservoir of hot water. Not sure of the model, if it is important
I can root through my boxes and find out.


Yes some models have the ability to do this.
In general, to keep the boiler in warm standby is about 30s every 30
minutes.

The OP was having the boiler run more than that.



--
Ed Sirett - Property maintainer and registered gas fitter.
The FAQ for uk.diy is at http://www.diyfaq.org.uk
Gas fitting FAQ http://www.makewrite.demon.co.uk/GasFitting.html
Sealed CH FAQ http://www.makewrite.demon.co.uk/SealedCH.html
Choosing a Boiler FAQ http://www.makewrite.demon.co.uk/BoilerChoice.html
Gas Fitting Standards Docs he http://www.makewrite.demon.co.uk/GasFittingStandards
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
combi boiler - pressure increases then boiler shuts down peri UK diy 1 July 10th 06 09:50 PM
Help - I have a back boiler and want a combi boiler fitted but have plastic pipes! Vikki Home Repair 1 November 22nd 05 11:51 PM
how much does it cost change back boiler to combi boiler [email protected] UK diy 5 October 10th 05 05:38 PM
WICKS combi 82, Halstead combi boiler [email protected] UK diy 3 September 12th 05 02:02 AM
Complicated central Heating; Back-Boiler and Combi-Boiler tfc715 UK diy 1 February 3rd 05 05:30 PM