Should Feed and Expansion tanks bulge?
Ongoing situation at "Big Sister's" house...
I asked in here a few months ago about various problems with Big Sis's plumbing, however, time moved on and her leaking plumbing disappeared and she set her sights on getting the whole plumbing replaced when she could find a plumber prepared to take on the job... Then, yesterday, her leak came back with a vengance. She apppears to have an indirectly heated hot water system (standard cylinder, 3-port valve, boiler downstairs, water pump etc), with a feed and expansion tank installed a couple of foot above the cylinder, all contained within an airing cupboard type of arrangement. The leak appears to be coming somewhere from the Feed and Expansion tank. Unfortunately, this sits on a piece of delaminating plywood which acts as a sponge, so wherever the leak is, it drips into the plywood which distributes is over the complete area of the airing cupboard making tracing the leak very difficult. Coupled to the fact that the F&E tank size is pretty much the internal dimensions of the airing cupboard makes the whole thing a right bugger to work on. Last night, having fused the CH circuit from water dripping onto the electrics (sigh!), I went around to take a closer look. Having removed the architrave surround to get a glimpse of the feed (and overflow) pipework going to the F&E tank, I was somewhat alarmed to see that the side of the tank that takes the feed/overflow buldged to an extent that there was a horizontal deflection of some 4-5 cm halfway down the side of a 50cm tall tank. To me it looked wrong, and could indicate where the tank has failed / is leaking. but until I can get there as a respectable plumbing time (i.e. not 9pm, and when I've charged my torch [hate it when they die after 2 mins use], and when I've got a set of step-ladders with me) I couldn't investigate further. In fact, I'm of the mind to replace the tank anyway. So, to a question or two... Is it commonplace for F&E tanks to incorporate such a large "buldge" in the design. Is it the considered opinion of those that deal with such stuff that this is likely to represent the point of failure of the tank? How much would a replacement tank cost (existing tank approx 80cm wide, 50cm deep, 50 cm high)? (I've tried online but there're few hits on F&E tanks, closest I got was loft tanks in Screwfix) [actually, cold light of day, their "10500" 25gal tank looks ok - is a loft tank the same as a F&E tank?) |
#2
Posted to uk.d-i-y
|
|||
|
|||
Should Feed and Expansion tanks bulge?
How many connection points on the tank? Presumably feed (with a ball
valve), outlet and an overflow. Water level is probably below 2 of those, so either the outlet leaks, the coupling to the ball valve leaks (which is presumably full mains pressure) or the tank is split. Must be a substantial leak to fuse the electrics. I'd expect a pvc tank to deform considerably before it would split, but it might cause a leak round the tank fitting if it's been badly placed. |
#3
Posted to uk.d-i-y
|
|||
|
|||
Should Feed and Expansion tanks bulge?
|
Reply |
Thread Tools | Search this Thread |
Display Modes | |
|
|
Similar Threads | ||||
Thread | Forum | |||
Wierd bulge appeared on hot water cylinder | UK diy | |||
how to bung combined feed / expansion?? | UK diy | |||
Expansion vessel on mains cold water feed to combi boiler | UK diy | |||
Leaking heating system (feed & expansion cistern drains) | UK diy | |||
Does having an Expansion Tank on your Water Heater make the water meter move? | Home Repair |