Default Expansion vessel in combi losing pressure. No water leaking from valve.


The boiler is a Chaffeteaux Britony 80 Combi. The expansion vessel
loses all pressure quickly.

After suspecting the vessel, I depressed the valve's plunger and found
that no air came out. I pumped it up with a bicycle pump so that the
pressure guage read 0.7bar more than it was before. An hour later, the
pressure had dropped back to where it was, and no air came out of the
valve when I depressed the plunger.

No water seeped from the valve when I depressed the plunger. I'm
wondering if the valve could be the culprit. Are these the same valves
that they use in car tyres? Is it as simple as going to a car spares
shop and asking for a tyre valve?

Thank you,

Jake
  #2   Report Post  
Posted to uk.d-i-y
Roger Mills \(aka Set Square\)
 
Posts: n/a
Default Expansion vessel in combi losing pressure. No water leaking from valve.

In an earlier contribution to this discussion,
Jake S wrote:

The boiler is a Chaffeteaux Britony 80 Combi. The expansion vessel
loses all pressure quickly.

After suspecting the vessel, I depressed the valve's plunger and found
that no air came out. I pumped it up with a bicycle pump so that the
pressure guage read 0.7bar more than it was before. An hour later, the
pressure had dropped back to where it was, and no air came out of the
valve when I depressed the plunger.

No water seeped from the valve when I depressed the plunger. I'm
wondering if the valve could be the culprit. Are these the same valves
that they use in car tyres? Is it as simple as going to a car spares
shop and asking for a tyre valve?

Thank you,

Jake


Did you do all this with the water system cold, and unpressurised? If not,
you need to do that.

To test the valve, re-inflate it to 0.7 bar and then spit on your finger and
wipe it over the end of the valve. A bubble will form if the valve is
leaking. If the vessel loses pressure, but the valve *isn't* leaking, the
vessel itself must be duff - in which case, I can't understand why no water
comes out of the valve.
--
Cheers,
Roger
______
Please reply to newsgroup.
Reply address IS valid, but is disposable in the event of excessive
spam.


Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
What's wrong with my central heating system? Jim T UK diy 7 October 31st 04 04:04 PM
Water Pump / Pressure Tank Problem !!!!!! James Nipper Home Repair 9 June 28th 04 02:13 AM
Water Pump / Pressure Tank Problem !!!!!! James Nipper Home Ownership 6 June 28th 04 02:13 AM
I need a little advice on running waterlines in an uninsulated crawlspace ozark Home Repair 12 January 29th 04 05:23 AM
Water Reduction Valves & Expansion Tanks John Gregory Home Repair 15 January 29th 04 03:00 AM


All times are GMT +1. The time now is 06:37 PM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"