I have a Vokera Excell 80 SP that has developeda fault. The central heating
stays on regardless of the temprature setting on the thermostat and stays on
even when the bolier is switched to summer \ water only mode.

I tried following the flow diagrams in the manual and this led to replacing
the easiet to replace but unfortunately the most expensive part, the PCB.
However, this has made no difference. Heating still fires up in both modes,
only way to turn it off temporarily (without setting the mode selector to
off) is by turning the central heating temperature setting dial on the
bolier to the minumum setting. Only problem with that is that the hot water
dosent work at the setting as it only seems to come when the heating is
fired up.

Any ideas?


  #2   Report Post  
Posted to uk.d-i-y
tarquinlinbin
 
Posts: n/a
Default Combination Boiler SOS

On Thu, 09 Feb 2006 16:38:28 GMT, "muthaleech"
wrote:

I have a Vokera Excell 80 SP that has developeda fault. The central heating
stays on regardless of the temprature setting on the thermostat and stays on
even when the bolier is switched to summer \ water only mode.

I tried following the flow diagrams in the manual and this led to replacing
the easiet to replace but unfortunately the most expensive part, the PCB.
However, this has made no difference. Heating still fires up in both modes,
only way to turn it off temporarily (without setting the mode selector to
off) is by turning the central heating temperature setting dial on the
bolier to the minumum setting. Only problem with that is that the hot water
dosent work at the setting as it only seems to come when the heating is
fired up.

Any ideas?

Is there a frost stat anywhere by any chance?



Remove antispam and add 670 after bra to email
  #3   Report Post  
Posted to uk.d-i-y
muthaleech
 
Posts: n/a
Default Combination Boiler SOS


"tarquinlinbin" wrote in message
...
On Thu, 09 Feb 2006 16:38:28 GMT, "muthaleech"
wrote:

Is there a frost stat anywhere by any chance?



Thanks for the reply.

Yes there is (according to the wiring diagram), I think I tried taking it
out of the equation but disconnecting one of the wires that went into the
block that it attaches to but this had no effect. I'll try bridging the
connection instead...


Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Running a combination boiler without central heating connected? Dave Fawthrop UK diy 22 September 3rd 05 07:37 AM
*Small* gas combination boiler? Dave Fawthrop UK diy 16 August 31st 05 11:53 PM
New condensing boiler installation - truth or lies Martin Evans UK diy 57 July 2nd 05 02:13 PM
Remove Radiator - Drain Combination Boiler heinzy UK diy 5 June 25th 05 05:32 PM
Condensing Boiler News RedOnRed UK diy 0 April 9th 05 05:37 PM


All times are GMT +1. The time now is 07:04 AM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"