Default Underground electrical conduit

I was blessed with about 800' of 2.5" underground pvc, which I intend to use
to run power to my shop area, about 150' from the house. My ground is all
blowsand mixed with lava rocks from fist sized to Volkswagen sized. I do
have a trencher, but after using it in other areas of my property, have
little faith or expectations for it other than it breaking another tooth.
Is it that important to have this buried that deep, or that it have a grade?
I will run sweeps up so that it is above ground by at least 3' at the
vertical. I intend to put two in the same ditch in case I ever want to run
other lines. As I understand it, Red Hot Blue Glue is good for this pipe.

Any caveats or suggestions?

Steve


  #2   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 1,934
Default Underground electrical conduit


"SteveB" wrote in message
...
I was blessed with about 800' of 2.5" underground pvc, which I intend to
use to run power to my shop area, about 150' from the house. My ground is
all blowsand mixed with lava rocks from fist sized to Volkswagen sized. I
do have a trencher, but after using it in other areas of my property, have
little faith or expectations for it other than it breaking another tooth.
Is it that important to have this buried that deep, or that it have a
grade? I will run sweeps up so that it is above ground by at least 3' at
the vertical. I intend to put two in the same ditch in case I ever want to
run other lines. As I understand it, Red Hot Blue Glue is good for this
pipe.

Any caveats or suggestions?



18" deep is all that you need although deeper is better in case of future
excavation. I suggest that you put a marker tape just below the soil
surface in case you or someone else digs where the pipe is in the future.

Just regular PVC glue should suffice although it is not a bad idea to use a
primer first. Be sure to put glue on each of the ends that are getting
pushed together.

  #3   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 747
Default Underground electrical conduit

On Aug 24, 4:30*pm, "SteveB" wrote:
I was blessed with about 800' of 2.5" underground pvc, which I intend to use
to run power to my shop area, about 150' from the house. *My ground is all
blowsand mixed with lava rocks from fist sized to Volkswagen sized. *I do
have a trencher, but after using it in other areas of my property, have
little faith or expectations for it other than it breaking another tooth.
Is it that important to have this buried that deep, or that it have a grade?
I will run sweeps up so that it is above ground by at least 3' at the
vertical. *I intend to put two in the same ditch in case I ever want to run
other lines. * As I understand it, Red Hot Blue Glue is good for this pipe.

Any caveats or suggestions?

Steve


I had one like that run a few years ago, we got by with a big ride on
trencher with rock chain except for a bout 50' where the backhoe was
required. The depth depends on the activities anticipated. I farm, so
3' would be a bare minimum, or risk snagging it with a chisel plow or
something. we went more like 41/2- 5', I'd have to use the auger or
backhoe to hit that. So long as you keep it well marked, it could be
shallow unless local codes say otherwise.
  #4   Report Post  
Posted to alt.home.repair
Joe Joe is offline
external usenet poster
 
Posts: 2,837
Default Underground electrical conduit

On Aug 24, 4:30*pm, "SteveB" wrote:
I was blessed with about 800' of 2.5" underground pvc, which I intend to use
to run power to my shop area, about 150' from the house. *My ground is all
blowsand mixed with lava rocks from fist sized to Volkswagen sized. *I do
have a trencher, but after using it in other areas of my property, have
little faith or expectations for it other than it breaking another tooth.
Is it that important to have this buried that deep, or that it have a grade?
I will run sweeps up so that it is above ground by at least 3' at the
vertical. *I intend to put two in the same ditch in case I ever want to run
other lines. * As I understand it, Red Hot Blue Glue is good for this pipe.

Any caveats or suggestions?

Steve


Ask your power company what they recommend. Locally, AmerenIP uses 3"
conduit at 42" for underground services, but your own building codes
for an outbuilding should be the proper guide.

Joe
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
How to seal ends of underground conduit ?? Andy Home Repair 1 January 13th 08 08:37 PM
How to seal ends of underground conduit ?? S. Barker Home Repair 1 January 9th 08 03:25 AM
How to seal ends of underground conduit ?? aemeijers Home Repair 0 January 8th 08 03:47 AM
Putting NM cable underground in conduit [email protected] Home Repair 4 November 16th 06 03:35 AM
Replacing underground conduit section scott moore Home Repair 6 April 21st 06 07:02 PM


All times are GMT +1. The time now is 07:44 AM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"