  #1   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 74
Default Plumbing: What size hot water pipe do I need?

I need to run hot water to lavatories, sinks, tubs, showers, washing
machine, dishwasher and a 60 gallon whirlpool tub in my home. Especially
for the sinks and lavatories I would like to use the smallest size pipe
that will provide sufficient flow. Lavatories and sinks often use
relatively small amounts of hot water at a time (wash hands, rinse
something). I think a smaller pipe would result in less waste and less
waiting for the water to get hot.

Appliances such as tubs, etc. are used less frequently and use much more
hot water at a time, so the initial wait and the waste of the ho****er left
in the pipe should not matter so much and a high flow rate is more
important.

Running separate pipes of different sizes to the same bathroom is no
problem if it will improve performance & save energy. I realize that
running the lavatory faucet and a tub/shower would require filling two
pipes, but this will seldom be done at the same time so the water in the
pipe would cool down between the uses.

Question: What size pipe should I run to each type of appliance?

Lavatory:
Sink:
Tub/Shower:
Whirlpool: 3/4" as valve inlets are 3/4"
Dishwasher:
Washing Machine:

Thanks so much for your help.
  #2   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 6,199
Default Plumbing: What size hot water pipe do I need?

On Apr 3, 6:23�am, wrote:
I need to run hot water to lavatories, sinks, tubs, showers, washing
machine, dishwasher and a 60 gallon whirlpool tub in my home. �Especially
for the sinks and lavatories I would like to use the smallest size pipe
that will provide sufficient flow. �Lavatories and sinks often use
relatively small amounts of hot water at a time (wash hands, rinse
something). �I think a smaller pipe would result in less waste and less
waiting for the water to get hot.

Appliances such as tubs, etc. are used less frequently and use much more
hot water at a time, so the initial wait and the waste of the ho****er left
in the pipe should not matter so much and a high flow rate is more
important.

Running separate pipes of different sizes to the same bathroom is no
problem if it will improve performance & save energy. �I realize that
running the lavatory faucet and a tub/shower would require filling two
pipes, but this will seldom be done at the same time so the water in the
pipe would cool down between the uses.

Question: �What size pipe should I run to each type of appliance?

Lavatory:
Sink:
Tub/Shower:
Whirlpool: �3/4" as valve inlets are 3/4"
Dishwasher:
Washing Machine:

Thanks so much for your help.


are you running PEX ? individual lines to each outlet has lots of
advantages, and be certain to insulate all hot water lines
  #3   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 74
Default Plumbing: What size hot water pipe do I need?

Yes, I am running PEX. I am planning to run a line to my kitchen sink and
then to a veggie sink because they are close together and will frequently
be used together.

On Thu, 3 Apr 2008 04:37:06 -0700 (PDT), "
wrote:

On Apr 3, 6:23?am, wrote:
I need to run hot water to lavatories, sinks, tubs, showers, washing
machine, dishwasher and a 60 gallon whirlpool tub in my home. ?Especially
for the sinks and lavatories I would like to use the smallest size pipe
that will provide sufficient flow. ?Lavatories and sinks often use
relatively small amounts of hot water at a time (wash hands, rinse
something). ?I think a smaller pipe would result in less waste and less
waiting for the water to get hot.

Appliances such as tubs, etc. are used less frequently and use much more
hot water at a time, so the initial wait and the waste of the ho****er left
in the pipe should not matter so much and a high flow rate is more
important.

Running separate pipes of different sizes to the same bathroom is no
problem if it will improve performance & save energy. ?I realize that
running the lavatory faucet and a tub/shower would require filling two
pipes, but this will seldom be done at the same time so the water in the
pipe would cool down between the uses.

Question: ?What size pipe should I run to each type of appliance?

Lavatory:
Sink:
Tub/Shower:
Whirlpool: ?3/4" as valve inlets are 3/4"
Dishwasher:
Washing Machine:

Thanks so much for your help.


are you running PEX ? individual lines to each outlet has lots of
advantages, and be certain to insulate all hot water lines


  #5   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 655
Default Plumbing: What size hot water pipe do I need?

Just run 3/4 to the first place, and then 1/2" to the second device. No
need to get fancy, you won't save anything.

s


wrote in message
...
I need to run hot water to lavatories, sinks, tubs, showers, washing
machine, dishwasher and a 60 gallon whirlpool tub in my home. Especially
for the sinks and lavatories I would like to use the smallest size pipe
that will provide sufficient flow. Lavatories and sinks often use
relatively small amounts of hot water at a time (wash hands, rinse
something). I think a smaller pipe would result in less waste and less
waiting for the water to get hot.

Appliances such as tubs, etc. are used less frequently and use much more
hot water at a time, so the initial wait and the waste of the ho****er
left
in the pipe should not matter so much and a high flow rate is more
important.

Running separate pipes of different sizes to the same bathroom is no
problem if it will improve performance & save energy. I realize that
running the lavatory faucet and a tub/shower would require filling two
pipes, but this will seldom be done at the same time so the water in the
pipe would cool down between the uses.

Question: What size pipe should I run to each type of appliance?

Lavatory:
Sink:
Tub/Shower:
Whirlpool: 3/4" as valve inlets are 3/4"
Dishwasher:
Washing Machine:

Thanks so much for your help.





  #6   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 4,764
Default Plumbing: What size hot water pipe do I need?

On Apr 3, 7:41 am, wrote:
Yes, I am running PEX. I am planning to run a line to my kitchen sink and
then to a veggie sink because they are close together and will frequently
be used together.


All you'll need to know.
http://www.toolbase.org/PDF/DesignGu...esignguide.pdf

R
  #7   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 775
Default Plumbing: What size hot water pipe do I need?

... be certain to insulate all hot water lines

How much energy would we save by adding R2 insulation to 100' of 1/2" pipe,
with 6 10 gallon hourly 110 F water uses per day at 3 gpm (an SRCC standard
test condition)?


The pipe is only used for about 3 minutes per hour...

Hint: not much, since there isn't much water in 1' of pipe,


.... 62.33Pi(0.5/24)^2 = 0.085 pounds.

so it cools fast between uses, even with lots of insulation.


L' of ri' radius pipe with an r' insulation radius and a k Btu/h-F-ft
insulation conductivity and an airfilm conductance h Btu/h-F-ft^2 would have
thermal resistance R = (1/(hr)+ln(r/ri)/k)/(2PiL), so 1' of bare 1/2" pipe
with ri = r = 0.3125/12 = 0.026' and an h = 1.5 slow-moving airfilm would
have R = 1/(1.5x0.026x2Pi) = 4.1 F-h/Btu, so RC = 4.1x0.085 = 0.35 hours,
ie 21 minutes. After 57 minutes in 70 F house air the 8.5 pounds of water
would cool from 110 to 70+(110-70)e^(-57/21) = 72.7 F, losing (110-72.7)8.5
= 317 Btu of heat.

With 1/2" of R4 per inch (R48 per foot, ie k = 0.021) foam insulation,
r = 0.6875/12 = 0.0573' and R = (1/(1.5x0.0573)+ln(0.0573/0.026)/0.021)/2Pi
= 7.8, so RC = 0.67 hours, ie 40 minutes, and the water cools from 110 to
70+(110-70)e^(-57/40) = 79.6 F, losing (110-79.6)8.5 = 258 Btu.

The net savings is 6(317-258) = 352 Btu per day or 129K Btu (38kWh) per year,
worth $3.80 at 10 cents/kWh.

OTOH, some pipe insulation near the heater where the pipes are warm most of
the time could pay for itself quickly.

Nick

  #8   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 6,199
Default Plumbing: What size hot water pipe do I need?

On Apr 4, 7:08�am, wrote:
... be certain to insulate all hot water lines


How much energy would we save by adding R2 insulation to 100' of 1/2" pipe,
with 6 10 gallon hourly 110 F water uses per day at 3 gpm (an SRCC standard
test condition)?


The pipe is only used for about 3 minutes per hour...

Hint: not much, since there isn't much water in 1' of pipe,


... 62.33Pi(0.5/24)^2 = 0.085 pounds.

so it cools fast between uses, even with lots of insulation.


L' of ri' radius pipe with an r' insulation radius and a k Btu/h-F-ft
insulation conductivity and an airfilm conductance h Btu/h-F-ft^2 would have
thermal resistance R = (1/(hr)+ln(r/ri)/k)/(2PiL), so 1' of bare 1/2" pipe
with ri = r = 0.3125/12 = 0.026' and an h = 1.5 slow-moving airfilm would
have R = 1/(1.5x0.026x2Pi) = 4.1 F-h/Btu, so RC = 4.1x0.085 = 0.35 hours,
ie 21 minutes. After 57 minutes in 70 F house air the 8.5 pounds of water
would cool from 110 to 70+(110-70)e^(-57/21) = 72.7 F, losing (110-72.7)8.5
= 317 Btu of heat.

With 1/2" of R4 per inch (R48 per foot, ie k = 0.021) foam insulation,
r = 0.6875/12 = 0.0573' and R = (1/(1.5x0.0573)+ln(0.0573/0.026)/0.021)/2Pi
= 7.8, so RC = 0.67 hours, ie 40 minutes, and the water cools from 110 to
70+(110-70)e^(-57/40) = 79.6 F, losing (110-79.6)8.5 = 258 Btu.

The net savings is 6(317-258) = 352 Btu per day or 129K Btu (38kWh) per year,
worth $3.80 at 10 cents/kWh.

OTOH, some pipe insulation near the heater where the pipes are warm most of
the time could pay for itself quickly.

Nick


remember in the winter the lost heat helps warm your home............

in summer it can be a loser if you air condition.

definetely insulate the lines but PEX is much less conductive heat
wise than copper, so its naturally a insulator.

life is full of standby losses..........

every electrical device in your home thats not 100% off when
off.......

cable boxes, computers, pilot lights, clocks, night lights, security
lights, TVs, the list is endless..........

one shouldnt get too concerned wany single one.

better to insulate and weatherstrip your home for better
savings............

you will likely save more
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
flue pipe size for venting water heater bill allemann Home Repair 2 August 28th 07 01:55 AM
Plumbing - Pipe size question [email protected] Home Repair 12 May 26th 07 02:59 PM
plumbing - water source pipe to the new house Martino Home Repair 3 January 12th 07 04:29 PM
Water pipe size PipeDown Home Repair 14 August 3rd 05 08:01 PM
Effect of pipe size on water flow rate? Dave UK diy 8 October 1st 04 01:04 PM