Default Old Lennox Furnace - Model GH6 100T (maybe thermostat maybe furnace problem)

In the last several days my thermostat and furnance don't seem to be
""talking"" to each other properly.

It seems that when I leave my thermostat alone it activates the
furnance to go on when called upon. If I want to do a manual override
on the thermostat it doesnt activate the furnace at all.

The contact points on the control (in furnace) do seem greasy but is
that enough to have my heating system behave in this way?

Jack



  #2   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 3,515
Default Old Lennox Furnace - Model GH6 100T (maybe thermostat maybe furnace problem)

jack posted for all of us...

In the last several days my thermostat and furnance don't seem to be
""talking"" to each other properly.

It seems that when I leave my thermostat alone it activates the
furnance to go on when called upon. If I want to do a manual override
on the thermostat it doesnt activate the furnace at all.

The contact points on the control (in furnace) do seem greasy but is
that enough to have my heating system behave in this way?

Jack




Asked and answered MANY times - do your own research.
--
Tekkie Don't bother to thank me, I do this as a public service.
  #3   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 2
Default Old Lennox Furnace - Model GH6 100T (maybe thermostat maybe furnace problem)

It would be just as easy to post the fix as it would to post "answered
already, do your own research". Thx for the tip...

Tekkie® wrote:
jack posted for all of us...

In the last several days my thermostat and furnance don't seem to be
""talking"" to each other properly.

It seems that when I leave my thermostat alone it activates the
furnance to go on when called upon. If I want to do a manual override
on the thermostat it doesnt activate the furnace at all.

The contact points on the control (in furnace) do seem greasy but is
that enough to have my heating system behave in this way?

Jack




Asked and answered MANY times - do your own research.
--
Tekkie Don't bother to thank me, I do this as a public service.


  #4   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 1
Default Old Lennox Furnace - Model GH6 100T (maybe thermostat maybe furnace problem)

duradrinx had written this in response to
http://www.thestuccocompany.com/main...ma-165203-.htm
:
I really hate to bump up a very old post. But I am having this exact
issue.

I had replaced my old mercury thermostat and shortly after this started
happening to me. I had the furnace looked at 3 times, 2 differant
companies. All three techs told me it has to be the thermostat. Well
after trying 2 more thermostats, differant manufacturers. Nothing has
changed.

Did anyone find a solution to this?






##-----------------------------------------------##
Delivered via http://www.thestuccocompany.com/
Building Construction and Maintenance Forum
Web and RSS access to your favorite newsgroup -
alt.home.repair - 322608 messages and counting!
##-----------------------------------------------##
  #5   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 330
Default Old Lennox Furnace - Model GH6 100T (maybe thermostat maybe furnace problem)


"duradrinx" wrote in message
om...
duradrinx had written this in response to
http://www.thestuccocompany.com/main...ma-165203-.htm
:
I really hate to bump up a very old post. But I am having this exact
issue.

I had replaced my old mercury thermostat and shortly after this started
happening to me. I had the furnace looked at 3 times, 2 differant
companies. All three techs told me it has to be the thermostat. Well
after trying 2 more thermostats, differant manufacturers. Nothing has
changed.

Did anyone find a solution to this?

I suggest you put back the old thermostat.

But one "clue" might be found by asking yourself how the thermostat gets the
power (I ASSume it is one of those electronic gadgets with a display.)

The old mercury thermostats are near idiot proof. They can even work on
"milivolt" system where the power to turn on the gas valve comes from a
thermopyle soaking in the pilot flame. If it just calls for heat it only
needs 2 wires. If it allow you to turn the fan on it only requires 3
wires. If there is an A/C with the furnace it only requires 1 more wire.







  #6   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 4,500
Default Old Lennox Furnace - Model GH6 100T (maybe thermostat maybefurnace problem)

On Nov 8, 9:12*pm, "John Gilmer" wrote:
"duradrinx" wrote in message

om... duradrinx had written this in response to
http://www.thestuccocompany.com/main...ox-Furnace-Mod...
:
I really hate to bump up a very old post. *But I am having this exact
issue.


I had replaced my old mercury thermostat and shortly after this started
happening to me. *I had the furnace looked at 3 times, 2 differant
companies. *All three techs told me it has to be the thermostat. *Well
after trying 2 more thermostats, differant manufacturers. Nothing has
changed.


Did anyone find a solution to this?


I suggest you put back the old thermostat.

But one "clue" might be found by asking yourself how the thermostat gets the
power (I ASSume it is one of those electronic gadgets with a display.)

The old mercury thermostats are near idiot proof. * *They can even work on
"milivolt" system where the power to turn on the gas valve comes from a
thermopyle soaking in the pilot flame. * *If it just calls for heat it only
needs 2 wires. * If it allow you to turn the fan on it only requires 3
wires. * If there is an *A/C with the furnace it only requires 1 more wire.



Forget about power or the furnace or anything else. If the furnace
always comes on as it should when the thermostat is left in the run
program mode and only fails to come on when you override it, then it's
either a bad thermostat or operator error. Also, the thermostat and
the furnace don't "talk to each other". The thermostat is just a
couple of switches that close to activate the furnace or just blower
seperately, etc. So, if that switch is closing in the "run program
mode", but not when you override it, it's only the two above
possibilities.
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Carrier Infinity Control thermostat problem [email protected] Home Repair 30 May 28th 15 02:29 AM
How do I know if furnace thermocouple is bad? [email protected] Home Repair 16 November 2nd 06 03:28 AM
Gas Furnace Air Flow problem Sean M Home Ownership 1 May 22nd 05 12:28 AM
To anyone sick of alt.hvac Matt Morgan Home Repair 87 April 8th 05 05:17 PM
Metal Working Machinery New and Used in Australia and for Export [email protected] Metalworking 0 February 23rd 05 02:54 AM


All times are GMT +1. The time now is 10:47 AM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"