Default How much air pressure to blow out sprinkler system ??

A friand of mine bought a new house, complete with a built in sprinkler
system. With cold weather coming, he knows he needs to winterize the
system, which is equipped with a quick-connect air fitting. He's
assuming he's supposed to hookup an air hose and purge the system with
air. Question is : how much pressure to use ?? ?? ??
  #2   Report Post  
SQLit
 
Posts: n/a
Default How much air pressure to blow out sprinkler system ??


"__ Bob __" wrote in message
...
A friand of mine bought a new house, complete with a built in sprinkler
system. With cold weather coming, he knows he needs to winterize the
system, which is equipped with a quick-connect air fitting. He's
assuming he's supposed to hookup an air hose and purge the system with
air. Question is : how much pressure to use ?? ?? ??



Your looking for volume not pressure per say.
Are you going to remove the heads or just blow it out?

If your going to blow it out then use 200 psi, and let me know when so I
can come by with my camera.


  #3   Report Post  
Steve Kraus
 
Posts: n/a
Default How much air pressure to blow out sprinkler system ??

What is the normal working pressure? Just city water main pressure?
What's that, about 50 psi or something? Probably no need to exceed working
pressure and a bad idea I would think, if you are leaving the heads in
place. The other idea, if there is water in the section you need to blow
out, is just to ease on the pressure gradually and watch the water flow out
the drain at the other end using just enough pressure to do this. If it's
a fairly flat run between the two point then only a few lbs would probably
do it. If you have verticals connecting floors then a bit more.

Is there a way you could push 50/50 antifreeze/water solution through the
affected area so it could just sit there?

This is just reasonable speculation. Maybe someone more knowledgeable will
know for sure.
  #4   Report Post  
DaveG
 
Posts: n/a
Default How much air pressure to blow out sprinkler system ??


"Steve Kraus" wrote in message
k.net...
What is the normal working pressure? Just city water main pressure?
What's that, about 50 psi or something? Probably no need to exceed
working
pressure and a bad idea I would think, if you are leaving the heads in
place. The other idea, if there is water in the section you need to blow
out, is just to ease on the pressure gradually and watch the water flow
out
the drain at the other end using just enough pressure to do this. If it's
a fairly flat run between the two point then only a few lbs would probably
do it. If you have verticals connecting floors then a bit more.

Is there a way you could push 50/50 antifreeze/water solution through the
affected area so it could just sit there?

This is just reasonable speculation. Maybe someone more knowledgeable
will
know for sure.


There are a couple websites which explain this process. Try Rainbirds site,
or do searches.
Don't confuse pressure with volume. You need a high volume compressor,
which most homeowners don't have. You can rent a high volume compressor, or
just pay someone who does this service.
We're talking 25+ CFM airflow at a relatively low pressure- 20 psi or
lower.
Do not equate water pressure with air pressure. If you go with 50 psi, you
may end up blowing your sprinkler heads into orbit, and or melting your
sprinkler components. Compressed air gets hot.
You can't use a typical 120v air compressor (6 - 10 cfm) and make up for
the low airflow by increasing the pressure.


  #5   Report Post  
 
Posts: n/a
Default How much air pressure to blow out sprinkler system ??

"Do not equate water pressure with air pressure. If you go with 50
psi, you
may end up blowing your sprinkler heads into orbit, and or melting your

sprinkler components. Compressed air gets hot.
You can't use a typical 120v air compressor (6 - 10 cfm) and make up
for
the low airflow by increasing the pressure. "

LOL!

The sprinkler system works with over 50PSI water pressure, but 50PSI
air pressure is going to blow it up? Or melt them? Now that is really
hysterical! Sure, air gets hot when it's compressed, which is why the
compressor gets hot. But when air expands, which is what it'd doing
when it leaves the compressor and goes into the sprinkler system, it
gets cold. That's how an air conditioner works.

I've blown mine out for 8 years with a 6 CFM Sears unit with maybe an 8
gallon tank. I let the pressure build to about 60 lbs, then turn on
one zone. Let it run for a couple mins, then turn off the zone, let
the pressure build back up, then do the next zone. Go through this
process twice for each zone. It's not as fast as using a high CFM
compressor, but it has worked well for me and saved me $500 so far!

Also, if you google, you'll find another recent thread on the same
topic.

Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
New condensing boiler installation - truth or lies Martin Evans UK diy 57 July 2nd 05 02:13 PM
What's wrong with my central heating system? Jim T UK diy 7 October 31st 04 04:04 PM
Regulator pressure increases over time - why?? David Home Repair 10 October 26th 04 01:16 AM
Charge pressure for sealed CH system Roger Mills UK diy 4 November 3rd 03 07:14 PM
Bowl Saving: A Comprehensive Discussion Ray Sandusky Woodturning 8 August 3rd 03 04:05 PM


All times are GMT +1. The time now is 07:26 PM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"