Terminating SWA at insulated consumer unit
"Andy Hall" wrote in message
...
Do you have a suggested way of terminating onto the tag?
I'd use a brass screw and a multiplicity of nuts (as a patent agent would
put it) through the small hole in the tag in conjunction with a crimped ring
terminal lug on the end of the earthing wire.
With care it's possible to bend the end of the tag over thro' 90° so that
the connection is entirely inside the enclosure. Do this if you're using a
plastic box because you don't really want a joint relying on pressure
applied through plastic parts which might creep.
--
Andy
|